Sunday, February 5, 2017

Techshore Inspection Services : ROTAMETER:


The name rotameter was chosen in the past because at one time the float was designed with slots to produce a rotational movement for the purpose of centering and stabilizing the float.



The float is free to move up or down within the tapered tube. The tube is tapered to provide linear relationship between the flow rate and the float position within the tube. The fluid enters at the bottom and passes upward around the float and out at the top. The float rises and falls depending on the flow rate, giving a variable area of the annular passage. The upward hydraulic forces that act on the float are in balance with its weight less the buoyant force; this will maintain the float position in equilibrium. The scale shows flow rate in percent.


The rotameter sizing is also based on Bernoulli’s theorem. Rotameters may be used to measure gas or liquids and even some light slurry. Therefore, the sizing where very low flows are measured, capacities are usually given in cc/minute of air or water: this rotameter equation used for the head meter also applies to the rotameter:




C:\Users\user\Desktop\rotameter (1).jpg
The same fundamental equation used for the head meter also applies to the rotameter:
                Q =KA√(2gh)
In this equation the differential pressure (h) is replaced by the factor that causes it to remain constant. This factor denotes the volume and area of the float as well as the density of the float and the fluid.
C:\Users\user\Desktop\Rotameter.jpg
The equation will be:
Q = kAm √ ((2g Vf/Af) * (Df / (D-1))
Where:
Q = Flow Rate
K = Taper Constant
Am = Annular area measured at indicating edge
G = gravity
Vf = Float Volume
Af = Float Area
Df = Float Density
D = Fluid Density
The rotameter may be subjected to error due to changes in the fluid density small variations in fluid viscosity will not affect measurements if the float is designed to be insensitive to them. This will make Df/D = 2. Therefore (Df/(D-1)) = 1.
Since √1=1, the effect of density is eliminated. The float also must be designed to ignore small changes in the viscosity of the fluid. The rotameter available with a tapered glass tube or metal tube. The choice of tube depends on the application. Where toxic or flammable fluids are to be measured, a metal tube is selected for the rotameter. However in this case the float is not visible and a different indication technique is required. The linear movement of the float must be converted into a rotating movement for local indication or signal transmission. The metering float is extended with a permanent magnet on top of it. Glass tubes are limited up to use for low pressure say 20 Kg/cm2.


Thursday, December 29, 2016

TECHSHORE INSPECTION SERVICES : PYROMETERS

                                      PYROMETERS
Temperature measurement by using thermocouples, RTDs and thermistors requires the sensors should be placed in physical contact with the medium or the object being measured, either directly or within a thermo well.
However, in some applications, contact measurement is not suitable. At high temperature the physical contact of the temperature sensors is not practical because it may melt. To solve this problem a non – contact method of temperature measuring is used. Also for bodies that are moving a non contact method of temperature sensing is most convenient.
Pyrometry is a technique for measuring temperature without contact. When a body is heated, it emits thermal energy known as heat radiation. A black body is a very good absorber of heat radiation.

OPTICAL PYROMETERS
Optical Pyrometers provide an accurate method of measuring temperature between 600 to 40000C and are very useful for checking and calibrating radiation pyrometers. But they are not suitable for recording and controlling temperatures.The method of operation of optical pyrometers is based on the comparison of intensity of the visual radiation emitted by the hot body by the source of known intensity. The brightness of radiation emitted by the hot body whose temperature is to be measured is matched with the brightness of a calibrated reference temperature whose temperature is known it consists of an incandescent lamp filament which is used as the reference source of radiation. This is kept in the field of vision of telescope, through which the filament and the hot body are viewed simultaneously.

Figure shows the schematic arrangement of optical pyrometer.
Wheatstone bridge circuit across which the moving coil galvanometer is connected. The electrical resistance varies according to the temperature, where the other arms of the wheat stones bridge do not change their resistance due to its temperature change. This is achieved by selecting materials whose ohmic value does not alter due to change in temperature. As the temperature of the filament increased the bridge progressively becomes imbalanced. The magnitude of imbalance is shown in galvanometer. This is calibrated in terms of temperature and the pointer deflection is read as the temperature which is equal to the temperature of the hot body. The filament is heated by a 2V battery in series with a rheostat by which the brightness of the filament is adjusted.


In this operation the hot object is viewed through the telescope. The filament 1st appears as a dark line against the bright ground as shown in the figure. On rotating the rheostat the brightness of the radiation matches the hot object. At that time the tip of the filament becomes invisible against the background. When this stage is achieved the temperature of the hot body can be read of from the galvanometer. An absorption screen is used between the hot object and the filament that reduces the intensity of the radiation from the hot body and the filament may be matched at lower temperature through the hot object may be at a much higher temperature. A monochromatic red screen is fixed to the eyepiece which will facilitate matching and also prevent the dazzle at higher temperatures.



Saturday, September 24, 2016

Techshore Turbine Flow meter

Turbine flow meter
Instrumentation mainly deals with different types of process variables such as flow, level, temperature and pressure. Sensors are the devices used to sense these process variables. Turbine flow meter is a major flow measuring sensor. Flow is mainly classified into three types based on the Reynolds number value. They are laminar flow, turbulent flow and transitional flow. For measuring turbulent as well as transitional flows only we are using turbine flow meter. Based on the turbine principle only the flow meter is working. At both the inlet and outlet side of the turbine flow meter so many pipelines will be provided and this will help to have a straight flow. As this flow enters inside the flow meter the turbine inside it will be starts rotating based on the pressure excreted. The movement of the turbine will be directly proportional flow rate. As the turbine moves the movement will be counted by the magnetic pickup which is placed above the turbine. The increase in count indicated by the magnetic pickup indicates the increase in flow rate and vice versa. A transmitter section is also inbuilt inside this sensor. So the output produced will be 4-20 mA.

Turbine Flow meter

Turbine flow meter

Instrumentation mainly deals with different types of process variables such as flow, level, temperature and pressure. Sensors are the devices used to sense these process variables. Turbine flow meter is a major flow measuring sensor. Flow is mainly classified into three types based on the Reynolds number value. They are laminar flow, turbulent flow and transitional flow. For measuring turbulent as well as transitional flows only we are using turbine flow meter. Based on the turbine principle only the flow meter is working. At both the inlet and outlet side of the turbine flow meter so many pipelines will be provided and this will help to have a straight flow. As this flow enters inside the flow meter the turbine inside it will be starts rotating based on the pressure excreted. The movement of the turbine will be directly proportional flow rate. As the turbine moves the movement will be counted by the magnetic pickup which is placed above the turbine. The increase in count indicated by the magnetic pickup indicates the increase in flow rate and vice versa. A transmitter section is also inbuilt inside this sensor. So the output produced will be 4-20 mA.