Showing posts with label Inspection. Show all posts
Showing posts with label Inspection. Show all posts

Sunday, February 5, 2017

Techshore Inspection Services : Half Cell Electrical Potential method

Principle
The half-cell electrical potential method is used to measure the potential of an embedded reinforcing bar relative to a reference half-cell placed on the concrete surface. The half-cell usually used is a copper/copper sulphate or silver/silver chloride cell but other combinations are also used. The concrete functions as an electrolyte and the risk of corrosion of the reinforcement near the test location may be related empirically to the measured potential difference. ASTM C876 - 91 gives a Standard method for testing Half-cell potential of uncoated reinforcing steel in concrete.
Equipment
The testing apparatus consists of the following components:
  • Copper-Copper Sulphate Half-Cell:
The cell consists of a rigid tube made of dielectric material which is non-reactive with copper or copper sulphate, a porous wooden or plastic plug which remains wet by capillary action, and a copper rod which is immersed within the tube in saturated copper sulphate solution. The solution is prepared by dissolving reagent grade copper sulphate crystals in distilled or de ionized water.
The inside diameter of rigid tube should not be less than 25 mm and that of porous tube should not be less than 13 mm. The immersed copper rod should have inner diameter of not less than 6 mm and length 50 mm.
  • Electrical junction device:
An electrical junction device is used to provide a low electrical resistance liquid path between the concrete surface and the half-cell. It consists of a sponge pre-wetted with a low electrical resistance contact solution. The sponge can be attached to the tip of the half-cell so that it provides electrical continuity between the porous tip and the concrete member.
  • Electrical contact solution:
Electrical contact solution is used to wet the electrical junction device so that the potential drop through the concrete portion of the circuit is standardized. It is a prepared by thoroughly mixing a 95 ml of wetting agent or a liquid household detergent with 19 L of potable water.
  • Voltmeter:
A battery operated voltmeter is used with ± 3% end of scale accuracy at the voltage ranges in use. The input impedance should be not less than 10 MW while operating at a full scale of 100 mV.
  • Electrical lead wires:
The electrical lead wire should be such that its electrical resistance for the required length does not disturb the electrical circuit by more than 0.0001 V.
Procedure
Measurements are made in a grid pattern. The spacing between the measurements is generally chosen such that adjacent readings are less than 150 mV with the minimum spacing so that there is at least 100 mV between readings. An area of high corrosion activity is indicated by the area with greater than150 mV. A direct electrical connection is made to the reinforcing steel using a compression clamp.
To get a low electrical resistance connection, the rod must be scraped before connecting it to the reinforcing bar. The reinforcement bar is connected to the positive terminal of the voltmeter. A lead wire is used to connect the half-cell to the negative terminal of the voltmeter. Before the test begins, the concrete surface has to be pre-wetted with a wetting agent. Areas in the member where corrosion activity may be occurring can be represented using an equipotential contour map.
The potential risks of corrosion based on potential difference readings are shown in Table 1 below:
Table 1. Risk of Corrosion against the potential difference readings
Potential difference levels (mv)
Chance of re-bar being corroded
Less than –500
Visible evidence of corrosion
-350 to -500
95%
-200 to -350
50%
More than -200
5%

Best Oil And Gas Institute In Kerala
Best Oil And Gas Institute In Kochi
Best Oil And Gas Institute In Kaloor
Best Oil And Gas Institute In Kollam
Best Oil And Gas Institute In Calicut
Best Oil And Gas Institute In Trivandrum
Best Oil And Gas Institute In Karnataka
Best Oil And Gas Institute In Pathanamthitta
Best Oil And Gas Institute In Mannar
Best Oil And Gas Institute In Kottayam
Best Oil And Gas Institute In Perumbavoor
Best Oil And Gas Institute In Telangana
Best Oil And Gas Institute In Tamilnadu
Best Oil And Gas Institute In Mumbai
Best Oil And Gas Institute In Bahrain
Best Qa/Qc Institute In Kerala
Best Qa/Qc Institute In Kochi
Best Qa/Qc Institute In Kaloor
Best Qa/Qc Institute In Kollam
Best Qa/Qc Institute In Calicut
Best Qa/Qc Institute In Trivandrum
Best Qa/Qc Institute In Karnataka
Best Qa/Qc Institute In Pathanamthitta
Best Qa/Qc Institute In Mannar
Best Qa/Qc Institute In Kottayam
Best Qa/Qc Institute In Perumbavoor
Best Qa/Qc Institute In Telangana
Best Qa/Qc Institute In Tamilnadu
Best Qa/Qc Institute In Mumbai
Best Qa/Qc Institute In Bahrain
Best Mep Institute In Kerala
Best Mep Institute In Kochi
Best Mep Institute In Kaloor
Best Mep Institute In Kollam
Best Mep Institute In Calicut
Best Mep Institute In Trivandrum
Best Mep Institute In Karnataka
Best Mep Institute In Pathanamthitta
Best Mep Institute In Mannar
Best Mep Institute In Kottayam
Best Mep Institute In Perumbavoor
Best Mep Institute In Telangana
Best Mep Institute In Tamilnadu
Best Mep Institute In Mumbai
Best Mep Institute In Bahrain
Best Instrumentation Institute In Kerala
Best Instrumentation Institute In Kochi
Best Instrumentation Institute In Kaloor
Best Instrumentation Institute In Kollam
Best Instrumentation Institute In Calicut
Best Instrumentation Institute In Trivandrum
Best Instrumentation Institute In Karnataka
Best Instrumentation Institute In Pathanamthitta
Best Instrumentation Institute In Mannar
Best Instrumentation Institute In Kottayam
Best Instrumentation Institute In Perumbavoor
Best Instrumentation Institute In Telangana
Best Instrumentation Institute In Tamilnadu
Best Instrumentation Institute In Mumbai
Best Instrumentation Institute In Bahrain
Best Fire And Safety Institute In Kerala
Best Fire And Safety Institute In Kochi
Best Fire And Safety Institute In Kaloor
Best Fire And Safety Institute In Kollam
Best Fire And Safety Institute In Calicut
Best Fire And Safety Institute In Trivandrum
Best Fire And Safety Institute In Karnataka
Best Fire And Safety Institute In Pathanamthitta
Best Fire And Safety Institute In Mannar
Best Fire And Safety Institute In Kottayam
Best Fire And Safety Institute In Perumbavoor
Best Fire And Safety Institute In Telangana
Best Fire And Safety Institute In Tamilnadu
Best Fire And Safety Institute In Mumbai
Best Fire And Safety Institute In Bahrain
Best Hvac Institute In Kerala
Best Hvac Institute In Kochi
Best Hvac Institute In Kaloor
Best Hvac Institute In Kollam
Best Hvac Institute In Calicut
Best Hvac Institute In Trivandrum
Best Hvac Institute In Karnataka
Best Hvac Institute In Pathanamthitta
Best Hvac Institute In Mannar
Best Hvac Institute In Kottayam
Best Hvac Institute In Perumbavoor
Best Hvac Institute In Telangana
Best Hvac Institute In Tamilnadu
Best Hvac Institute In Mumbai
Best Hvac Institute In Bahrain
Best Logistics Institute In Kerala
Best Logistics Institute In Kochi
Best Logistics Institute In Kaloor
Best Logistics Institute In Kollam
Best Logistics Institute In Calicut
Best Logistics Institute In Trivandrum
Best Logistics Institute In Karnataka
Best Logistics Institute In Pathanamthitta
Best Logistics Institute In Mannar
Best Logistics Institute In Kottayam
Best Logistics Institute In Perumbavoor
Best Logistics Institute In Telangana
Best Logistics Institute In Tamilnadu
Best Logistics Institute In Mumbai
Best Logistics Institute In Bahrain
Best Ndt Institute In Kerala
Best Ndt Institute In Kochi
Best Ndt Institute In Kaloor
Best Ndt Institute In Kollam
Best Ndt Institute In Calicut
Best Ndt Institute In Trivandrum
Best Ndt Institute In Karnataka
Best Ndt Institute In Pathanamthitta
Best Ndt Institute In Mannar
Best Ndt Institute In Kottayam
Best Ndt Institute In Perumbavoor
Best Ndt Institute In Telangana
Best Ndt Institute In Tamilnadu
Best Ndt Institute In Mumbai
Best Ndt Institute In Bahrain
Best Automation Institute In Kerala
Best Automation Institute In Kochi
Best Automation Institute In Kaloor
Best Automation Institute In Kollam
Best Automation Institute In Calicut
Best Automation Institute In Trivandrum
Best Automation Institute In Karnataka
Best Automation Institute In Pathanamthitta
Best Automation Institute In Mannar
Best Automation Institute In Kottayam
Best Automation Institute In Perumbavoor
Best Automation Institute In Telangana
Best Automation Institute In Tamilnadu
Best Automation Institute In Mumbai
Best Automation Institute In Bahrain
Best Concrete Ndt Institute In Kerala
Best Concrete Ndt Institute In Kochi
Best Concrete Ndt Institute In Kaloor
Best Concrete Ndt Institute In Kollam
Best Concrete Ndt Institute In Calicut
Best Concrete Ndt Institute In Trivandrum
Best Concrete Ndt Institute In Karnataka
Best Concrete Ndt Institute In Pathanamthitta
Best Concrete Ndt Institute In Mannar
Best Concrete Ndt Institute In Kottayam
Best Concrete Ndt Institute In Perumbavoor
Best Concrete Ndt Institute In Telangana
Best Concrete Ndt Institute In Tamilnadu
Best Concrete Ndt Institute In Mumbai
Best Concrete Ndt Institute In Bahrain
Best Electrical Qc Institute In Kerala
Best Electrical Qc Institute In Kochi
Best Electrical Qc Institute In Kaloor
Best Electrical Qc Institute In Kollam
Best Electrical Qc Institute In Calicut
Best Electrical Qc Institute In Trivandrum
Best Electrical Qc Institute In Karnataka
Best Electrical Qc Institute In Pathanamthitta
Best Electrical Qc Institute In Mannar
Best Electrical Qc Institute In Kottayam
Best Electrical Qc Institute In Perumbavoor
Best Electrical Qc Institute In Telangana
Best Electrical Qc Institute In Tamilnadu
Best Electrical Qc Institute In Mumbai
Best Electrical Qc Institute In Bahrain,

Monday, January 2, 2017

TECHSHORE INSPECTION SERVICES : WELL TESTING

WELL TESTING
More   and   more    importance   is  being   placed   upon  efficient   performance   of   oil  and   gas  wells. Generally   some   kind   of   testing should  be done   to   determine  the   performance   of  an   oil  or  gas  well . There   are  many  types tests ,to check certain parameters about the well. Many tests are done often and some are done rarely.
Some   of   the   well   tests   are   simple  and  some   are   complicated .Standard production   equipments are only needed for many tests, but  special equipments are required for others. These tests are to be done carefully because the results reflects the health of the well. These tests are done for the company to plan proper production procedures and to meet regulatory requirements . It   is  very   important  that   the   test   be   done   accurately   since  well   test   data   documents   the   performance  of   a   well  and   the   reservoir  in   which   the  test   is  completed . Very   often   these  tests   are   performed   by  the   producer   to   help  in   establishing  proper   production  practices   and  to   comply   with   regulatory   requirement  .
There   are   many   types   of   well   tests   done  by lease    operators , well  testers, or  specialist  companies. Most   commonly   used  well  tests   are  discussed  below.


DRILL-STEM  TEST
When   well  is   being  drilled ,a   drill- stem  test   is   often  run  on  a   formation  of  unknown  performance  to  determine  if  a  formation  contains  oil ,  water , gas ,  or  a  combination  of the   three  .
These testing require special tools and packers which have to be run through the drill pipe to isolate the problem areas. Fluid is then allowed to flow from the formation to pass through the tester to the drill pipe. Fluid is then collected in a system of valves in the tester which is then collected for further examination. If there is sufficient pressure to cause the flow to the ground level, then productivity and capacity can be assessed.
Up This   procedure   requires  special  tools  and   packers  to  be  run  on  the  drill   pipe  to   isolate  the  interval  to   be   tested  .Fluid  is   thus allowed  to   flow  from  the  formation  ,through   the   tester, and finally to the drill   pipe . Fluid which is trapped in the drill pipe is collected by the system valve and its taken for further testing. If  the   formation  pressure   is   sufficient   to  cause    flow   to   the   surface , a  sustained  flow   test   through   the   drill  pipe  will  provide   a  measure  of   the  productivity and  capacity  of   the  interval   tested.
The   test   result   shows   the   bottom   hole  shut-  in   pressure ,  bottom – hole  flowing   pressure,and bottom-hole  temperature, and  the   type   of  fluid   in  the  well  might  be   capable   of   producing .
The   result   of  drill-stem  tests  on  a   well   will  often   h  if  a   casing   string   should  be   run  to  complete  the   well  as  a  producing   well  , or  if   the   well   is  a   dry   hole .This   information  is  used  as  the   design   basis   for   a   production   system  .

POTENTIAL   TEST 
 In   potential   test output of a well for a day (24 hrs) is measured in rigid conditions. This   test   is done  one very newly completed well. Sometimes this test is repeated when state   or federal   regulatory   agency   or   the   well-operator needs a potential report.

PRODUCTIVITY    TEST
Productivity   tests   are   made   on  both   oil  and  gas   wells  and  include   the   well  potential  and  bottom-hole  pressure   tests  .
Flow from reservoir to the well is caused by the pressure difference.High pressure in the reservoir will force the fluid to flow to the low pressure area in the well. Flow rate is proportional to the pressure difference..
During productivity test shut in pressure of the bottom hole is measured first .This pressure is known as the static/reservoir pressure.The well is then tested in different stable rates and the bottom pressures are carefully recorded.From this data an engineer can calculate the output from the well.In gas wells   the output potential is determined by measuring the atmosphearic pressure at the well mouth and the gas output..

.Best Oil And Gas Institute In Kerala
Best Oil And Gas Institute In Kochi
Best Oil And Gas Institute In Kaloor
Best Oil And Gas Institute In Kollam
Best Oil And Gas Institute In Calicut
Best Oil And Gas Institute In Trivandrum
Best Oil And Gas Institute In Karnataka
Best Oil And Gas Institute In Pathanamthitta
Best Oil And Gas Institute In Mannar
Best Oil And Gas Institute In Kottayam
Best Oil And Gas Institute In Perumbavoor
Best Oil And Gas Institute In Telangana
Best Oil And Gas Institute In Tamilnadu
Best Oil And Gas Institute In Mumbai
Best Oil And Gas Institute In Bahrain
Best Qa/Qc Institute In Kerala
Best Qa/Qc Institute In Kochi
Best Qa/Qc Institute In Kaloor
Best Qa/Qc Institute In Kollam
Best Qa/Qc Institute In Calicut
Best Qa/Qc Institute In Trivandrum
Best Qa/Qc Institute In Karnataka
Best Qa/Qc Institute In Pathanamthitta
Best Qa/Qc Institute In Mannar
Best Qa/Qc Institute In Kottayam
Best Qa/Qc Institute In Perumbavoor
Best Qa/Qc Institute In Telangana
Best Qa/Qc Institute In Tamilnadu
Best Qa/Qc Institute In Mumbai
Best Qa/Qc Institute In Bahrain
Best Mep Institute In Kerala
Best Mep Institute In Kochi
Best Mep Institute In Kaloor
Best Mep Institute In Kollam
Best Mep Institute In Calicut
Best Mep Institute In Trivandrum
Best Mep Institute In Karnataka
Best Mep Institute In Pathanamthitta
Best Mep Institute In Mannar
Best Mep Institute In Kottayam
Best Mep Institute In Perumbavoor
Best Mep Institute In Telangana
Best Mep Institute In Tamilnadu
Best Mep Institute In Mumbai
Best Mep Institute In Bahrain
Best Instrumentation Institute In Kerala
Best Instrumentation Institute In Kochi
Best Instrumentation Institute In Kaloor
Best Instrumentation Institute In Kollam
Best Instrumentation Institute In Calicut
Best Instrumentation Institute In Trivandrum
Best Instrumentation Institute In Karnataka
Best Instrumentation Institute In Pathanamthitta
Best Instrumentation Institute In Mannar
Best Instrumentation Institute In Kottayam
Best Instrumentation Institute In Perumbavoor
Best Instrumentation Institute In Telangana
Best Instrumentation Institute In Tamilnadu
Best Instrumentation Institute In Mumbai
Best Instrumentation Institute In Bahrain
Best Fire And Safety Institute In Kerala
Best Fire And Safety Institute In Kochi
Best Fire And Safety Institute In Kaloor
Best Fire And Safety Institute In Kollam
Best Fire And Safety Institute In Calicut
Best Fire And Safety Institute In Trivandrum
Best Fire And Safety Institute In Karnataka
Best Fire And Safety Institute In Pathanamthitta
Best Fire And Safety Institute In Mannar
Best Fire And Safety Institute In Kottayam
Best Fire And Safety Institute In Perumbavoor
Best Fire And Safety Institute In Telangana
Best Fire And Safety Institute In Tamilnadu
Best Fire And Safety Institute In Mumbai
Best Fire And Safety Institute In Bahrain
Best Hvac Institute In Kerala
Best Hvac Institute In Kochi
Best Hvac Institute In Kaloor
Best Hvac Institute In Kollam
Best Hvac Institute In Calicut
Best Hvac Institute In Trivandrum
Best Hvac Institute In Karnataka
Best Hvac Institute In Pathanamthitta
Best Hvac Institute In Mannar
Best Hvac Institute In Kottayam
Best Hvac Institute In Perumbavoor
Best Hvac Institute In Telangana
Best Hvac Institute In Tamilnadu
Best Hvac Institute In Mumbai
Best Hvac Institute In Bahrain
Best Logistics Institute In Kerala
Best Logistics Institute In Kochi
Best Logistics Institute In Kaloor
Best Logistics Institute In Kollam
Best Logistics Institute In Calicut
Best Logistics Institute In Trivandrum
Best Logistics Institute In Karnataka
Best Logistics Institute In Pathanamthitta
Best Logistics Institute In Mannar
Best Logistics Institute In Kottayam
Best Logistics Institute In Perumbavoor
Best Logistics Institute In Telangana
Best Logistics Institute In Tamilnadu
Best Logistics Institute In Mumbai
Best Logistics Institute In Bahrain
Best Ndt Institute In Kerala
Best Ndt Institute In Kochi
Best Ndt Institute In Kaloor
Best Ndt Institute In Kollam
Best Ndt Institute In Calicut
Best Ndt Institute In Trivandrum
Best Ndt Institute In Karnataka
Best Ndt Institute In Pathanamthitta
Best Ndt Institute In Mannar
Best Ndt Institute In Kottayam
Best Ndt Institute In Perumbavoor
Best Ndt Institute In Telangana
Best Ndt Institute In Tamilnadu
Best Ndt Institute In Mumbai
Best Ndt Institute In Bahrain
Best Automation Institute In Kerala
Best Automation Institute In Kochi
Best Automation Institute In Kaloor
Best Automation Institute In Kollam
Best Automation Institute In Calicut
Best Automation Institute In Trivandrum
Best Automation Institute In Karnataka
Best Automation Institute In Pathanamthitta
Best Automation Institute In Mannar
Best Automation Institute In Kottayam
Best Automation Institute In Perumbavoor
Best Automation Institute In Telangana
Best Automation Institute In Tamilnadu
Best Automation Institute In Mumbai
Best Automation Institute In Bahrain
Best Concrete Ndt Institute In Kerala
Best Concrete Ndt Institute In Kochi
Best Concrete Ndt Institute In Kaloor
Best Concrete Ndt Institute In Kollam
Best Concrete Ndt Institute In Calicut
Best Concrete Ndt Institute In Trivandrum
Best Concrete Ndt Institute In Karnataka
Best Concrete Ndt Institute In Pathanamthitta
Best Concrete Ndt Institute In Mannar
Best Concrete Ndt Institute In Kottayam
Best Concrete Ndt Institute In Perumbavoor
Best Concrete Ndt Institute In Telangana
Best Concrete Ndt Institute In Tamilnadu
Best Concrete Ndt Institute In Mumbai
Best Concrete Ndt Institute In Bahrain
Best Electrical Qc Institute In Kerala
Best Electrical Qc Institute In Kochi
Best Electrical Qc Institute In Kaloor
Best Electrical Qc Institute In Kollam
Best Electrical Qc Institute In Calicut
Best Electrical Qc Institute In Trivandrum
Best Electrical Qc Institute In Karnataka
Best Electrical Qc Institute In Pathanamthitta
Best Electrical Qc Institute In Mannar
Best Electrical Qc Institute In Kottayam
Best Electrical Qc Institute In Perumbavoor
Best Electrical Qc Institute In Telangana
Best Electrical Qc Institute In Tamilnadu
Best Electrical Qc Institute In Mumbai
Best Electrical Qc Institute In Bahrain,

Friday, December 30, 2016

TECHSHORE INSPECTION SERVICES : REBAR LOCATOR


Principle
The Principle of Rebar Locator is that it can be worked either by utilizing Eddy current effect or Magnetic induction effect.
In cover meters using eddy current effect, current in the search coil set up eddy currents in the reinforcement which in turn causes the measured impedance of the search coil to change. Instruments using this principle operate at above 1 kHz frequencies. They are thus sensitive to the presence of any conducting material in the vicinity of the search head.
In cover meters using magnetic induction effect, a multi coil search head is used with a lower operating frequency of less than 90 Hz compared to the eddy current type device. Here the principle used is similar to that of a transformer. In that one or two coils (acting as primary coil) carry the driving current while one or two further coils (acting as secondary coil) pick up the voltage transferred through the magnetic circuit formed by the search head and embedded reinforcing. Such instruments are less sensitive to the presence of magnetic materials in the vicinity of search head compared to those using the eddy current principle. When there is a change in the amount of ferromagnetic material under the search head due to the presence of reinforcing bar or other metal object, there is an increase in the field strength. This in turn, causes an increase in the voltage detected by the secondary coil, which can be displayed after amplification by the meter.
In both types of instruments the meter reading is affected by both the orientation and the proximity of the metal to the search head. Thus it can be used to locate reinforcing bars and determine their orientation. The cover to a bar can also be find out if a suitable calibration can be obtained for the particular bar size and the materials under investigation. Most instruments have a procedure to estimate both bar size and distance from the probe to the bar when neither is known.

Equipment
Equipment mainly consists of a number of suitable battery or mains operated cover meters. Each cover meter is comprised of a Search head, meter and an interconnecting cable. The concrete surface is scanned by keeping the search head in contact with it while the meter indicates the proximity of reinforcement by analogue or digital means.


Procedure
The Rebar Locator equipment is switched on. Then start the main menu function and select the single point test. Then select approximate diameter 16. After that fix the probe in vacuum and scan the probe with 90 degree to rebar direction. Whenever the beep sound comes, move the probe slowly and it means we are near the rebar. When the scroll bar gets maximum points stop the probe and select the OK button. The value shown is the total depth of concrete. Then move the probe slowly again and get maximum point in scroll bar and press menu button. Here we get two values. The first value is the diameter of rebar and second value is the rebar thickness.

Applications
Rebar Locator can be used for following applications:
·         For quality control by ensuring correct location and cover to reinforcing bars after the placement of concrete.
·         Investigation of concrete members whose records are not available or need to be rechecked
·         Location of reinforcement as a preliminary test to some other tests in which reinforcement should be avoided or its nature taken into account.

·         Location of buried ferromagnetic objects like water pipes, steel joints, lighting conduits etc.